Water cooled glycol chiller HTLT-30WD

Group W/C Glycol Chiller 3hp to 50hp
Min. Order 1 piece
Terms of Payment L/C, D/P, Western Union, T/T
Update Time 2017-07-15
Item specifics
Compressor brandDanfoss/SANYO/COPELAND
Pump brandMinamoto
Condensershell and tube
Power3ph 380v 50hz and 60HZ for option
Temperature displayPID
Temperature range-35C to 0C
RefrigerantR22, R407C
  • Description
  • Product review

HERO-TECH 30hp water cooled glycol chiller


HERO-TECH  Water cooled glycol chillers with featured advantages as following,

l  Low cost

l  Energy saving

l  Easy connection

l  Easy and convenient maintenance

l  High EER

l  Power:3PH 380V 50HZ

l  Compressor: DANFOSS, COPELAND hermetic scroll compressor

l  Chilled water temperature range: -35 to 0.

l  Refrigerant: R22, R407C or R404A charged,

l  Control: Microcomputer control system offering accurate temperature stability within ±1.

l  Safety devices: Multi-protection devices ensure the chiller unit running safely.



HTLT-WSeries Water Cooled Glycol Chiller Technical Specifications

Model

HTLT-30WD

Nominal Cooling Capacity

-10

KW

46.6

-20

29.4

-30

16.1

-35

13.8

Condenser

Type

 

Shell and tube type

Cooling water flow

-10

m3/h

10.4

-20

6.58

-30

3.74

-35

3.2

Inlet and Outlet Connection(BSP)

Inch

3

Evaporator

Type

 

Shell and tube/ss plate heat exchanger

Coolant volume

-10

m3/h

8.01

-20

5.06

-30

2.77

-35

2.37

Inlet and Outlet Connection(BSP)

Inch

2-1/2

Input power

KW

26.5

Power Source

 

3PH~380V~415V/50HZ

Refrigerant

Type

 

R22/R404A

Control

 

Thermostatic expansion valve

Compressor

Type

 

Hermetic Scroll(piston)

Motor power

KW

11.3*2

Pump

Power

KW

4

Max. head

m

25

Safety device

Inner thermostat for compressor motor, unit overload relay, high and low pressure switch, freeze protection thermostat, reverse phase protection relay, discharge gas thermostat flow switch.

Dimension

Length

mm

1900

Width

mm

910

Height

mm

1720

Net weight

KG

1150

           

NOTE: The specificationsbased on the following design conditions:

l  Condensingtemperature 50

l  Cooling airinlet/outlet temperature: 25/30

Wereserve the right to modify the specifications without further notice.